The GF1060C CT and VT comparator is a multifunctional, high-precision current and voltage transformer comparator. It is used to compare the secondary current signal or secondary voltage of a device under test or the digital information of a non-conventional transformer with the reference signal of a standard transformer. It is suitable for testing conventional electronic and non-conventional digital current & voltage measuring transformers.
■ Electrical laboratory;
■ Metrological service center;
■ ISO17025 electrical laboratory;
■ Power engineering commissioning company;
■ Electricity power bureau & power company;
■ National Metrology and testing department;
■ Current transformer and voltage transformer factory;
■ Electrical Department of industrial and mining enterprises;
■ IEC61850-9-2;
■ ANSI/IEEE C57.13;
■ IEC60044-1, IEC60044-2,IEC60044-6;
■ GB1207-2006, GB1208-2006, GB16847-1997;
■ IEC61869-1,IEC61869-2,IEC61869-8,IEC61869-10,IEC61869-14;
■ 1. Using traditional transformer calibration equipment to achieve value transmission;
■ 2. Using a 24 bit AD chip and 512 times oversampling to maximize bandwidth expansion and improve accuracy;
■ 3. Adopting multi gear automatic switching and FIR filter to improve dynamic range and reduce signal-to-noise ratio;
■ 4. Customize the testing plan through programming and automatically determine whether the test data is qualified;
■ 5. Real time display of waveform, frequency, amplitude, phase and other data, facilitating comprehensive analysis of transformer performance;
■ 6. Built in industrial computer with 8-inch color touch screen, easy and convenient operation;
■ 7. Equipped with powerful operating software;
■ 8. Statistically analyze the average value, variation, extremum, and multiple errors of ratio difference and phase difference, which can be used to analyze transformers conduct comprehensive verification of stability and linearity;
■ 9. Can perform multiple harmonic analysis and verify the accuracy of each harmonic of the transformer;
■ 10. Can record and replay the entire testing process;
■ 11. Equipped with impedance compensation error function.
■ 1. It is possible to verify the phase angle and ratio differences of traditional electromagnetic current transformers.
■ 2. Electronic current transformers (current sensors) with small signal output can be verified for ratio and phase angle differences.
■ 3. Work as a current transformer and voltage transformer reference comparator.
| Electrical parameters | |
|---|---|
| Accuracy class | 0.05%, 0.02% | 
| Power supply | AC 220V±10% or AC 110V±10% 50/60Hz | 
| Input Range | |
| Voltage range | 100V/√3V, 100V, 110V/√3V, 110V, 120V/√3V, 120V, 150V, 220V (max 265V AC) | 
| Current range | 0.2A, 1A, 5A, 10A (max 12A AC) | 
| Small signal 500mV range | 0-500mV AC | 
| Small signal 8.5V range | 0-8.5V AC | 
| Verification of traditional current transformers | |
| Accuracy class | 0.05 (Ratio error≤0.05%, Phase error≤2') | 
| Standard current measurement range | 1%~120%In, 0.05%RD (In=1A, In=5A) | 
| Tested current measurement range | 1%~120%In, 0.05%RD (In=1A,In=5A) | 
| Verification of electronic current transformers | |
| Standard current measurement range | 1%~120%In,0.05%RD (In=1A or In=5A) | 
| Tested small signal input voltage range | 1%~120%In,0~8.5V (Un=333mV, 1V) | 
| Verification of traditional voltage transformers | |
| Accuracy class | 0.05 (Ratio error≤0.05%, Phase error≤2') | 
| Standard voltage measurement range | 10%~120%In, 0.05%RD (Un=100/√3V,100V) | 
| Tested voltage measurement range | 10%~120%In, 0.05%RD (Un=100/√3V,100V) | 
| Verification of electronic voltage transformers | |
| Standard voltage measurement range | 10%~120%In, 0.05%RD (Un=100/√3V,100V) | 
| Tested small signal input voltage range | 1%~120%In, 0~8.5V (Un=8.5V) | 
| Tested small signal input voltage range | 5%~120%In, 0~8.5V (Un=500mV) | 
| Harmonic Output | |
| Accuracy | Ratio error: 0.1%Uh or 0.1%Ih (Uh is the effective value of the fundamental wave) Phase error: 10' (2-21st)  | 
                
| LCD | 8 inch touch TFT color LCD | 
| Operating key | Support mouse and keyboard(USB port) | 
| Communication port | USB, RS232, 10/100M Lan | 
| Standards | |
| Reference standards | GB1207-2006, GB1208-2006, GB16847-1997  IEC60044-1, IEC60044-2,IEC60044-6, IEC61869-1,IEC61869-2,IEC61869-8,IEC61869-10,IEC61869-14, IEC61850-9-2, ANSI/IEEE C57.13  | 
                
| Safety standards | GB 4793.1-2007 | 
| EMC | EMC standard 89/336/EEC | 
| FCC Subpart B of Part 15 class A | |
| IEC 1000-4-2/3/4/6 | |
| Mechanical parameters | |
| Overall dimension (L×W×H)(mm) | 410×200×340 | 
| Weight (kg) | 8.5 | 
| Environmental conditions | |
| Relative humidity | Relative humidity 5%-95% not condensing | 
| Operating temperature | 0°C to +50°C | 
| Storage temperature | -20°C to +70°C |